200V Class

Rated Input Voltage:

200 - 240VAC + 10%,
Three Phase (3Ø)
50/60Hz + 5%

Rated Output Voltage:

200 - 230V + 10%,
Three Phase (3Ø)
According to supply voltage.

XLT6 Series 230V  
Model Selection Table

HP Model kW kVA Output (A)
15 XLT6-150 11 16.8 44
20 XLT6-200 15 22.1 58
25 XLT6-250 18.5 27.8 73
30 XLT6-300 22 32.4 85
40 XLT6-400 30 43 113
50 XLT6-500 37 53.3 140
60 XLT6-600 45 64.3 169
75 XLT6-750 55 80 210
100 XLT6-1000 75 112.2 270
400V Class

Rated Input Voltage:

380 - 460VAC, +10%, 3Ø (only)
50/60Hz + 5%.

Rated Output Voltage:

380 - 460V + 10%, 3Ø
Corresponding to
supply voltage.

XLT6 Series, 460V  
Model Selection Table

HP Model kW kVA Output (A)
15 XLT6-151 11 18.2 22
20 XLT6-201 15 24.1 29
25 XLT6-251 18.5 30.7 37
30 XLT6-301 22 35.7 43
40 XLT6-401 30 47.3 57
50 XLT6-501 37 58.1 70
60 XLT6-601 45 70.1 85
75 XLT6-751 55 87.2 105
100 XLT6-1001 75 112.2 135
125 XLT6-1251 90 133 160
150 XLT6-1501 110 162.1 195
175 XLT6-1751 132 191.2 230
 
 
Control Method:
Line to line sine-wave pulse width modulation (PWM) control

Output Frequency Range:
0.1 - 400 Hz
To operate the beyond 50/60 Hz, 
consult the motor manufacturer 
about the maximum allowable speed

Frequency Accuracy:
Digital command: 
+
0.01% of the max. frequency
Analog command: 
+
0.2% (25C + 10C) of the max. frequency

Frequency Resolution:
Digital:     0.1 Hz
Analog:     Max. frequency/4000

V/F Characteristics:
V/F free setting, constant torque, and reduced torque of V/F control.

Overload Capacity:
120%, 30 Seconds
150%, 0.5 Seconds

Acceleration/Deceleration Time:
0.1 - 3600 sec. (linear/curve, accel./decel.), 
Two stage accel./decel. setting available

Braking:
Dynamic Braking
Built-in BRD circuit (Optional resistor) for 15, 20 HP only.
External dynamic braking unit (option) for 25 HP & above.
Braking resistor is not integrated in the inverter.
Please install optional braking resistor or dynamic braking unit when large control torque is required.

DC Braking -
 
Performs at start; under set frequency at deceleration,
or via an external input (braking force, time and operating
frequency)

Input Signal:
Frequency Setting -
Operator: 
Up(1) and Down(2) keys/value setting keys.
Potentiometer:
Set by potentiometer
External signal: 
DC 0 ~ 10 VDC, 
-10V to +10V  (input impedence 10k ohms), 
4 ~ 20 mA (input impedence 100k ohms)
External Port:
Set by RS485

Forward/Reverse/Start/Stop -
Operator:
 
Run key/Stop key  (FW/RV can be set by command)
External signal:
FW RUN/STOP (NO contact), RV set by terminal assignment (NO/NC selection), 3-wire input possible
External Port:
Set by RS485

Intelligent Input Terminals - 
Selection of 5 functions from:
RV (Reverse), CFI~CF4 (Multispeed command), JG (Jogging), DB (External DC braking), SET (Second motor constants setting), , 2CH (Second accel./decel.)
FRS (Free-run stop), EXT (External trip), USP (Unattended Start Protection), 
CS (Change to/from commercial power supply) SFT (Software lock), AT(Analog input selection), RS (Reset), STA (3-wire start), STP (3-wire stop), F/R (3-wire fwd./rev.), PID (PID On/Off), PIDC (PID reset), UP/DWN (Remote-controlled accel.decel.), UDC (Remote-controlled data clearing), SF1-SF7 (Multispeed bit command 1-7), OLR (Overload limit change), and NO (Not selected)

Thermistor Input - 
One terminal

Output Signal:
Intelligent Output Terminal - 
Two NO contacts and one NO-NC combined contact (Selection from: RUN, FA1, FA2, OL, OD, AL, FA3, IP, UV, RNT, ONT and THM)

Intelligent Monitor Output Terminal - 
Analog voltage, analog current, pulse line output

Display Monitor:
Output frequency, output current, scaled value of output frequency, trip history,
I/O terminal condition, input power, output voltage.

Other Functions:
V/F free setting (up to 5 points), frequency upper/lower limit, frequency jump, 
accel/decel curve selection, manual torque boost value and frequency adjustment, analog meter tuning, start frequency setting, carrier frequency setting, electronic thermal free-setting, external frequency output zero/span reference, external frequency input bias start/end, alalog input selection, retry after trip, restart after instantaneous power failure, various signal outputs, reduced voltage start, overload restriction, automatic energy saving.

Carrier Frequency Range:
0.5 - 12kHz

Protective Function:
Over-current protection, overload protection, braking resistor overload protection, over-voltage protection, EEPROM error, under-voltage error, CT(Current transformer) error, CPU error, external trip USP error, ground fault, input over-voltage protection, instantaneous power failure, option 1 connection error, option 2 connection error, inverter thermal trip, phase failure detection, IGBT error, thermistor error

Environmental Conditions:
Ambient Operating: -10 ~ 50ºC
Storage Temperature: -20 ~ 65ºC 
Humidity: 25 ~ 90 % RH(no condensation)
Vibration: 5.9 m/s^2 (0.6G), 10 ~ 55 Hz
Location: Less than 1000 m of altitude or less, indoors (no corrosive gases or dust)

Color:
Blue

Protective Structure:
IP20 (NEMA 1)

Options (cost extra):
EMI filters, input/output reactors, DC reactors, radio noise filters, braking resistors,braking units, LCR filter, multilingual operator with copy function, communication cables,option PCB

Standard Digital Operator:
OPE-SR (Cables (option): ICS-1(1m), ICS-3(3m))


FEATURES:

Automatic Energy Saving Function
With its Automatic Energy-saving Function, the  XKT6 delivers "real-time" energy-saving operation for your fan and pump applications.
      
The function insures that motor operates at minimum current in response to the torque required by the load.

Enhanced Input/Output Terminals
Three relay output terminals are provided as standard for flexible interface to external control systems.
     

Intelligent Input/Output Terminal System
The L300P features an intelligent control terminal system, which allows necessary drive 1/0 functions to be freely programmed. 
Input terminals can be selected for either sink or source type logic.

Easy-to-use Operator Panel
The L300P's operator panel supports various monitoring functions.

Output frequency                    Output terminals status 
Output current                        Converted value of output Rotational direction                                 Output voltage                             
PID feedback value                  Input voltage                           
Input terminals status              Cumulative operation time
Cumulative power-on time        Trip event counter, history
        
Easy-Removable Cooling Fan
Cooling fan(s) and DC bus capacitors can be easily changed in the field. 
A fan ON/OFF function can be activated to provide longer cooling fan life.

Removable Control Circuit Terminals
Eliminates control rewiring when field replacing.

User Friendly Operation
Ease of Operation with Digital Operator (OPE-SR)>
User Selection of Command Functions ("Quick Menu")
Built-In RS485
Programming Software 

Environmental Friendliness
EMI Filter Available
Reduced Noise From Control Power Supply

Global Performance
Conformity to global standards UL, cUL, CE, C-Tick
Network compatibility with 
LONWORKS, PROFIBUS, DeviceNet,
Modbus RTU, and 
Ethernet with communication options.